▒0.5░C temp; 0.03% rdg. process Resolution 1░/0.1░; 10 ╡V process Temperature Stability 0.08░C/░C; 50 ppm/░C process Thermocouple Cold End Tracking 0.05░C/░C NMRR 60 dB CMRR 120 dB A/D Conversion Dual slope Reading Rate 3 samples per second Digital Filter Programmable Display Dual 4-digit, 7-segment LED, 9.2 mm (0.36"); red process vari-able, green setpoint; indicators for output and alarm status; 7.6 mm (0.3") for NEMA 12 units Warmup to Rated Accuracy 30 min INPUT Input Types Thermocouple, RTD, analog voltage, analog current Thermocouple Lead Resistance 100 ohm max RTD Input 100/500/1000 ohm Pt sensor, 2, 3, or 4-wire; 0.00385 or 0.00392 curve Voltage Input 0 to 100 mV, 0 to 1 V, 0 to 10 Vdc Current Input 0 to 20 mA (5 ohm load) Configuration Single-ended Polarity Unipolar Step Response 0.7 sec for 99.9% Decimal Selection None, 0.1 or 0.01 Span Adjustment 0.001 to 9999 counts Offset Adjustment -999 to +9999 CONTROL Action Reverse (heat) or direct (cool) Modes Time proportioning and proportional control modes; selectable preset tune, adaptive tune, auto-tune, PID, proportional, proportional with integral, proportional with derivative with anti-reset windup, on-off Rate 0 to 999.9 sec Reset 0 to 99 min 59 sec Cycle Time 1 to 199 seconds; set to 0 for on/off operation Gain 0.5 to 100% of span; setpoints 1 or 2 Damping 0000 to 0008 Soak 00.00 to 99.59(HH:MM), or off Ramp to Setpoint 00.00 to 99.59(HH:MM), or off Autotune Operator initiated from front panel Break Protection Programmable up- or down-scale CONTROL OUTPUT Relay 5 A @ 120 Vac, 3 A @ 240 Vac; configurable for on/off, PID or ramp and soak SSR Rated 1 A @ 120/240 Vac, continuous DC Pulse non-isolated; 10 Vdc @ 20 mA Analog Output 0 to 10 Vdc or 0 to 20 mA; 500 ohm max OPTIONS Remote Setpoint Selection Up to 3 setpoints stored in memory; contact closure selection COMMUNICATIONS RS-232 or RS-485 300 to 19.2k baud; complete programmable setup capability; program to transmit current display, alarm status, min/max, actual measured input value and status RS-485 Addressable from 0 to 199 Connection Screw terminals ALARM 2 Type SPST relay, 3 A @ 120 Vac, 3 A @ 240 Vac Operation High/low, latching/ non-latching, and process/deviation; front panel con-figurations ANALOG OUTPUT Isolated 0 to 10 Vdc or 0 to 20 mA, programmable INSULATION* Power to Input or Output 2500V ac or dc. Except for Alarm 2 option that has only 1500Vac or dc. Between inputs 500Vac or dc. Approvals UL ISCE E136081, CE per EN50081-1, EN50082-1, EN61010- 1 GENERAL Power 90 to 240 Vac/dc, 50 to 400 Hz; 10 to 34 Vac/dc power optional Environmental Condition 0 to 55░C (32 to 131░F), 90% RH non-condensing Installation Category II per IEC1010 Equipment Class I per IEC1010 Polution Degree 2 per IEC1010 Power Consumption 5 VA max @ 120 Vac ICN77300 Series 48 H x 48 W x 123.3 mm D (1.89" x 1.89" x 4.85") Panel Cutout: 45 mm (1.777") square, 1/16 DIN ICN77500 Series 53 H x 53 W x 123.3 mm D (2.1" x 2.1" x 4.85") Panel Cutout: 45 mm (1.777") square, 1/16 DIN ICN77R300 Series 48 H x 48 W x 135 mm D (1.89" x 1.89" x 5.32") ICN77R500 Series 53 H x 53 W x 135 mm D (2.1" x 2.1" x 5.32") Panel Cutout: 44.5 mm (1.75") dia round Weight 227 g (0.5 lb) Note: * Power Line/Neutral to Earth 1500 Vac per 1 min. test, Earth to RS232/analogout 100Vdc, Input power to control 1 or 2 or Alarm 2 2500Vac, Alarm 2 to other Input/Output 1500Vac.
|